GUIDE TO FLUORESCENT LAMP BALLASTS
- Published by Advance Transformer Co.
- Reprint permission granted
General Information
Troubleshooting Fluorescent Lamp Ballasts
UNDERSTANDING LIGHT SOURCES
INCANDESCENT LAMPS
Even though nearly 90% of the energy consumed by incandescent
lamps is dissipated as heat, they are still prevalent in most
American homes and are used throughout business and industry.
Their operation is simple and self-regulating: when electricity
passes through the lamp's filament it heats until it glows (incandesces)
and produces light. The amount of light generated depends upon
the amount of electrical current that passes through the filament.
In addition to producing light, the filament also limits the
current to safe operating values. The quantity of light generated
by a lamp is measured in lumens.
THE ENERGY-EFFICIENT FLUORESCENT LAMP
Fluorescent lamps operate cooler than incandescent lamps and
are more efficient in using energy to create light. Rather than
using a standard filament, their operation relies upon an electrical
arc passing between two electrodes, one at either end of the
lamp. This arc is conducted by a mixture of vaporized mercury
and purified gases-mainly neon and krypton or argon-through a
tube lined with phosphor The resulting ultraviolet waves cause
the phosphor to glow and emit fluorescent light.
WHY FLUORESCENT LAMPS NEED BALLASTS
Unlike incandescent lamps, fluorescent lamps cannot be connected
directly to the line. Unless the flow of current is stabilized
in some manner, more and more current will rush through the lamp
until it becomes inoperable.
The length of an incandescent lamp's filament limits the amount
of electrical current passing through the lamp and regulates
its light output. However, the fluorescent lamp needs an additional
electrical device to regulate the current. This device is called
a ballast.
BALLAST FUNCTION
Fluorescent lamps sold in the U.S. today are available in a
wide variety of shapes and sizes. They range from miniature versions
rated at 4 watts, 6 inches in length with a diameter of 5/8 inches
to 215 watt models, 8 feet or more in length with diameters exceeding
2 inches.
Voltage required to start the lamps is dependent on lamp length
and diameter, with larger lamps requiring higher voltages. Each
fluorescent lamp must be operated by a ballast that is specifically
designed to provide the proper starting and operating voltage
required by that particular lamp.
In all fluorescent lighting systems, the ballast performs
two basic tasks:
- Provides the proper voltage to establish an arc between the
two electrodes
- Regulates the electric current flowing through the lamp to
stabilize light output
In some fluorescent lighting systems the ballast also provides
a controlled amount of electrical energy to preheat lamp electrodes.
To receive peak performance from fluorescent lighting it is
essential that the fluorescent lamp ballast-the heart of the
fluorescent fixture match precisely the requirements of the lamp
it is designed to operate.
Three major types of lighting system circuits are in use today:
Preheat, Slimline Instant Start and Rapid Start. Additionally,
two newer types of circuitry, Modified Rapid Start and Instant
Start of Rapid Start Lamps, have also been developed.
PREHEAT CIRCUIT
The Preheat circuit, which requires the lamp electrodes to be
preheated by a separate manual or automatic starter switch, was
the original system developed for the operation of fluorescent
lamps.
During the starting cycle, the ballast limits the current flow
to a calibrated value for preheating the electrodes. In a few
seconds the electrodes attain the proper temperature, at which
time the starting switch automatically opens. The opening of
the starting switch breaks the shunting wire path for the flow
of current, leaving the gas in the lamp as the only other path
to travel.
The Preheat circuit is generally used for low wattage linear
and compact lamps (4 to 30 watts).
SLIMLINE INSTANT START
The Slimline Instant Start system produces light instantly without
the assistance of a starter. To achieve this quick response,
without lamp filaments being preheated, the ballast must provide
an open circuit voltage to the lamp electrodes about three times
the normal lamp operating voltage to initiate the arc. This high
initial voltage requires a larger auto-transformer as an integral
part of the ballast.
A larger "choke coil" or "reactor" must
also be included to reduce the starting voltage to the rated
operating voltage of the lamp.
Two lamp Slimline ballasts are available in two circuit types:
Lead Lag and Series Sequence.
The Lead Lag Slimline Instant Start circuit differs from the
Preheat circuit in the starting voltage produced and the absence
of the lamp starters.
SERIES SEQUENCE CIRCUIT
To reduce the size, weight and cost of the Slimline Instant
Start Lead Lag Ballast' a Series Sequence Ballast was introduced.
In this ballast circuit two lamps are operated in series with
the lamps starting in sequence. This circuit was pioneered by
Advance.
The Series Sequence circuit differs from all others in that
each of the circuits performs a separate function. The starting
section supplies sufficient voltage and current to light one
lamp with the remaining lamp igniting in sequence from the same
voltage and current. Because the lamps are in series, the ballast
is not required to supply individual lamp currents.
The reduction in power requirements makes it possible to operate
Slimline instant Start Lamps with a fluorescent lamp ballast
which is lighter and more efficient at about one-third the size
of comparable Lead Lag types.
RAPID START CIRCUIT
Rapid Start lighting system circuits are today's most popular
design. Low voltage cathodes are automatically preheated by means
of heater windings built into the fluorescent lamp ballast. This
eliminates the need for a separate starting switch, although
the fixture must be properly grounded and the lamps positioned
within 1/2 inch (F40T12), 3/4 inch (F32T8) or 1 inch (800 MA
and 1500 MA) of the fixture for proper starting. Continuous lamp
filament heating is provided by the ballast after the lamps are
started.
Because of the continuously heated electrodes, less voltage
is required for the initial surge to start the lamp than with
Slimline Instant Start. Rapid Start Lamps light immediately at
low brightness and are fully lighted in about two seconds.
OTHER CIRCUIT TYPES
Modified Rapid Start and Instant Start of Rapid Start Lamps
are two new types of lighting system circuits that have recently
emerged.
Modified Rapid Start circuits start the lamps in the same manner
as Rapid Start circuits do, but do not maintain lamp filament
heating after the lamps ignite. The lamp filament heating is
reduced or eliminated to save energy.
ELECTROMAGNETIC BALLASTS
Because ballasts are essential to fluorescent lamp operation,
they have been available for as long as the lamps they start
and regulate. Throughout most of their history, fluorescent ballasts
have been electromagnetic. As a result of their design, these
ballasts are also called "core & coil" ballasts.
The primary component of an electromagnetic ballast is a core
of stacked steel laminations around which insulated copper or
aluminum coils are wound. This core & coil design functions
both as a voltage transformer and a current-limiting choke. As
heat produced by the ballast's operation can eventually break
down the insulation around the coils and cause failure, the core & coil
is "potted" in insulating material such as asphalt
to conduct the heat away from the coils. This assembly is usually
housed in a steel case.
The capacitor of an electromagnetic ballast improves its power
factor, so it can utilize energy more efficiently. An electromagnetic
ballast that is equipped with a capacitor is considered to be
a high power factor or power factor corrected ballast.
Electromagnetic ballasts are available as Preheat, Lead Lag'
Series Sequence and Rapid Start designs.
HYBRID BALLASTS
The hybrid ballast design combines the starting and operating
characteristics of the electromagnetic ballast with the energy
efficiencies of electronic circuitry to provide an alternative
means of operating rapid start lamps.
The construction of this ballast is identical to the electromagnetic
ballast in that it also uses a core & coil, a capacitor and
potting. This ballast also incorporates electronic circuitry
to disconnect the cathode heater windings after the lamp ignites.
The starting method for a hybrid ballast is identical to an electromagnetic
rapid start ballast. I he difference occurs during normal operation
when the cathode heaters are disconnected and the energy consumption
is reduced.
Hybrid ballasts are available as modified Rapid Start designs.
ELECTRONIC BALLASTS
Electronic ballasts provide the necessary voltage to start the
lamp and regulate the current through the lamps after ignition,
much like an electromagnetic ballast. The electronic ballast,
however, operates the lamp at a frequency of 20 kHz or greater
rather than the 60 Hz operation of electromagnetic and hybrid
types. This takes advantages of increased fluorescent lamp efficiencies
at these higher frequencies. This high frequency operation is
accomplished by using electronic circuitry which generally results
in a more efficient, smaller, lighter, and quieter ballast design
than the standard electromagnetic ballast.
Electronic ballasts are available as Rapid Start, Modified Rapid
Start and Instant Start designs.
CERTIFICATION
There are several organizations involved with ballast standards
and testing. They are:
- CBM-CERTIFIED BALLAST MANUFACTURERS ASSOCIATION, manufacturers
who produce fluorescent ballasts to conform to ANSI specifications
C82. 1, C82.11, C82.2, C82.3 and C78.
- ANSI-AMERICAN NATIONAL STANDARDS INSTITUTE, originates standards
on a national level. Composed of over 120 trade associations,
technical societies, professional groups and consumer organizations,
it creates standards and eliminates duplicates.
- ETL-ELECTRICAL TESTING LABORATORIES INC., a private, independent
organization, is a recognized authority in measurements and
testing of lamps and lighting equipment. Certified Ballast
Manufacturers Association retains Electrical Testing laboratories,
Inc., to test ballasts produced by members to ensure they conform
to ANSI and CBM specifications.
- UL-UNDERWRITERS LABORATORIES, INC., is an independent, not-for-profit
organization testing for public safety. Its function is, through
study, experiment and tests, to prevent the loss of life and
property from the hazards of fire, casualty and crime.
- CSA-CANADIAN STANDARDS ASSOCIATION, is the testing authority
for ballasts used in Canada.
- E-ENERGY EFFICIENT BALLAST, indicates ballast complies with
National Energy Conservation Amendments (NAECA) of 1988 to
Energy Policy and Conservation Act (EPCA) of 1987.
- CSA-E-Canadian Standards Association Energy Efficient Ballasts,
indicates ballast complies with Canadian Energy Standards.
SUPPLY VOLTAGE & FREQUENCY
Each ballast is designed to operate at the nominal voltage shown
on the Advance label. Abnormal deviation from these values will
result in damage to either the ballast or lamp or both. It is
therefore recommended that the voltage applied to ballasts bearing
the following nominal rating be maintained within the respective
limits shown:
Nominal Voltage |
Applied Voltage Limits |
120 |
112 - 127 |
208 |
199 - 216 |
220 |
210 - 230 |
240 |
225 - 250 |
250 |
235 - 260 |
277 |
255 - 290 |
347 |
322 - 365 |
480 |
450 - 500 |
* Electronic ballasts may operate over a wider voltage limit
of ± 10%.
Most ballasts are designed for single frequency operation; thus
best results will prevail when the ballast is used on the frequency
that is shown on the ballast label. Frequency limitations are
as follows:
Nominal |
Frequency Limits |
60Hz. |
57.5 to 62.5 |
50Hz. |
47.5 to 52.5 |
* Some electronic ballasts operate over a wider frequency range
POWER FACTOR
The power factor of a ballast is the measurement of how efficiently
it converts the voltage and current supplied from the power source
into watts of usable power delivered to the ballast. Perfect
utilization of electrical current would result in a power factor
of 100%. Power factor is not an indication of the ballast's ability
to supply light through the lamps.
POWER FACTOR |
= |
WATTS INPUT
LINE VOLTS X LINE AMPS |
Fluorescent ballasts are designated high power factor, normal
(low) power factor, or power factor corrected.
High power factor ballasts, which are specified for all commercial
lighting applications, are those having a ratio of watts delivered
to the ballast, compared to the volt-amperes supplied, of greater
than 90%(.9).
Because high power factor ballasts employ a lower operating
current' more fixtures can be installed per branch circuit. Lower
power factor ballasts require about twice the current needed
by high power factor ballasts. Low power factor ballasts create
added wiring costs, allow fewer fixtures per circuit, and can
load branch circuits as well as the circuits of the utility,
potentially resulting in penalty charges.
Advantage of High Power Factor Ballasts
1. Avoid possible penalty charges from electric utility.
2. Wiring costs are less because normal power factor ballasts
take about twice the line current of high power factor ballasts
and may require heavier wire to carry the load.
3. With high power factor ballasts, more fixtures can be installed
on each branch circuit.
CLASS P THERMAL PROTECTION
All indoor fluorescent fixtures must incorporate ballast thermal
protection according to the National Electrical Code. (Fixtures
employing a single reactive type ballast for linear lamps are
excepted.)
Ballasts meeting the standard are designated "Class P" by
Underwriters' Laboratories, Inc.
Advance Class P Magnetic and Hybrid ballasts incorporate the
protector within the ballast case. Operation of this thermally
actuated automatic reclosing protective device will disconnect
the ballast from the power line in the event of over temperature.
All Advance Electronic ballasts are Class P rated but may not
incorporate the protector in their design, these ballasts inherently
limit their case temperature below the Class P limits.
Advance Class P ballasts also help protect against excessive
voltage supply, internal ballast short circuiting, inadequate
lamp maintenance and improper fixture application. They also
eliminate the need for individual fixture fusing.
When replacing Class P or non-Class P ballasts be sure to use
an exact equivalent. (For instance, nuisance tripping may occur
if a non-Class P is replaced with a Class P ballast.)
FUSE PROTECTION
The wide use of Class P ballasts has reduced the need for fusing
of ballasts. Individual fusing is sometimes considered when many
fixtures operate on a single circuit and where it is desirable
to isolate an inoperative fixture quickly This helps avoid complete
circuit outage when troubleshooting.
If used, fuses should be of the slow-blow type and should accommodate
inrush current and abnormal starting cycle currents of the ballast.
Electronic ballasts generally have higher inrush current then
electromagnetic ballasts. This will not be a problem if the correct
fuse is specified.
BALLAST FACTOR
Ballast factor is the measurement of a ballast's ability to
produce light from fluorescent lamps. It is the ratio of light
output produced by lamps operating on a commercial ballast versus
the light output of the same lamps operating on a laboratory
reference ballast specified to ANSI standards for a given lamp
type.
BALLAST FACTOR |
|
COMMERCIAL BALLAST LIGHT OUTPUT
LABORATORY REFERENCE BALLAST (100% LIGHT OUTPUT) |
= |
A ballast may have different ballast factors for different lamps, e.g., standard lamps as compared to energy saving lamps.
BALLAST EFFICACY FACTOR
The ballast efficacy factor is a ratio of the ballast factor
(the ballast's ability to produce light) versus the watts input
to the ballast. This measurement is generally used to compare
the efficiencies of various ballasts with a given lamp.
BALLAST
EFFICACY FACTOR |
= |
BALLAST FACTOR
BALLAST WATT INPUT |
The higher the ballast efficacy factor, the more efficient the
ballast.
The higher the ballast efficacy factor, the more efficient the
ballast. When ballast efficacy factor is multiplied by the lumen
rating of the lamp, a ratio of lumens per watt is created which
can be used to compare different ballast/lamp systems.
CREST FACTOR
Crest factor is one of the criteria used by lamp manufacturers
to ensure fluorescent lamp life. A measurement of current supplied
by the ballast to the lamp, it is basically a ratio of peak current
to the root mean square (RMS) current values. Most lamp manufacturers
require a crest factor of 1.7 or less on electronic ballasts
in order for the lamp to be warrantied properly for its rated
life. Current that has a high crest factor can cause materials
to be eroded from lamp electrodes, prematurely shortening lamp
life.
TOTAL HARMONIC DISTORTION
Harmonics are currents or voltages which have frequencies that
are integer multiples of the fundamental power frequency. Each
has a name associated with the multiplying number, i.e, if the
fundamental frequency is 60 Hz, then the second harmonic is 120
Hz, the third is 180 Hz, etc.
Harmonics occur whenever the wave shape is distorted, i.e.,
when the wave shape varies from a pure sine wave.
Electric utilities typically generate a voltage which is very
nearly a sine wave. If an end user connects a linear load such
as a resistive heater, the resulting current will be a sine wave
and no harmonics will be present. If, however, the load is non-linear,
drawing short pulses of current within each cycle, the current
wave shape will be distorted (nonsinusoidal) and harmonic currents
will flow. The total current will be a combination of the fundamental
plus each of the harmonics. Total harmonic distortion (THD) is
the measurement of the magnitude of the input current harmonics
compared with the amplitude of the fundamental frequency current.
Harmonics are important because in three phase systems, certain
harmonic currents can overload neutral conductors. The troublesome
harmonics, called "triplens," consist of the 3rd and
odd multiples of the 3rd (i.e., 3rd, 9th, 1 5th, etc.). These
harmonics will add rather than cancel in the neutral of a three-phase
4-wire system. Therefore, if the triplen harmonics exceed 33
1/3, more current will flow in the neutral wire then any of the
phase wires, even if the phase currents are perfectly balanced.
EMI/RFI
Radio and TV interference is caused by the action of the arc
at the lamp electrodes which creates a series of radio waves.
This energy may interfere with radio reception and the operation
of other communications equipment.
Types of interference:
1. Direct radiation from the fluorescent lamp to the aerial
circuit.
2. Line feedback from the lamp/ballast through the power line
to the radio.
3. Direct radiation from the electric supply line to the aerial
circuit.
To correct the first cause, it is recommended that the radio
and aerial circuit be separated at least 10 feet from the fluorescent
lamp and the radio provided with a positive ground.
The second and third causes can be corrected in lighting systems
that generate objectionable radio interference by additional
filtering. Generally this can be accomplished by the addition
of an external capacitor-reactor filter It is also desirable
for the radio and fluorescent lamp fixture to be provided with
a supply voltage from separate branch circuits.
Electronic ballasts which operate the lamp at high frequency
may also affect the operation of infrared, powerline carrier
and communications equipment. There may be no correction possible
for some of these interference problems so care must be taken
when specifying a lighting installation.
BALLAST SOUND
The slight hum present in fluorescent lighting installation
originates from vibration caused by the inherent magnetic action
in the core & coil assembly of the ballasts. There are three
possible ways this sound may be amplified:
1. Method of mounting the ballast in the fixture.
2. Loose parts in the fixture.
3. Ceilings, walls, floors and furniture.
The choice of fluorescent lamp ballasts should be made on the
basis of selecting the one rated quietest for a specific location.
Ballasts are assigned a sound rating, Class A through F, based
on the amount of noise produced. Because electronic ballasts
lack vibrating parts, and have higher operating frequencies,
they generally produce less noise and achieve a lower sound rating.
To make the best selection, the application needs must be considered.
It is obvious that consideration of ballast sound is more important
in a boardroom than in a busy store. See chart for assistance
in selecting the proper sound rated ballast.
SOUND RATINGS
For any installation In: |
Average Ambient Noise Level Of Interior: |
Sound Level Rating* |
TV or Radio Station, Library, Reception or Reading Room, Church, School Study Hall |
20-24
DECIBELS |
A |
Residence, Quiet Office, Night
School Classroom |
25-30
DECIBELS |
B |
General Office Area, Commercial
Building, Storeroom |
31-36
DECIBELS |
C |
Manufacturing Facility, Retail
Store, Noisy Office |
37-42
DECIBELS |
D |
*These sound ratings are based on measurements of Average Ambient noise levels
during conditions of normal occupancy. Audible ballast hum may appear amplified
during exceptionally quiet periods and at times when area is unoccupied
Note: In planning a lighting installation, careful consideration
must be given to the selection of the ballast, the lighting fixture
and the room components in the early planning stages to ensure
the quietest lighting installation possible.
COLD WEATHER OPERATION
Low temperatures in cold weather applications such as outdoors
and walk-in freezers can effect lamp starting and operation.
Lumen ratings of fluorescent lamps apply for operation in still
air that has a temperature of 25° C (77° F . While many
fluorescent lamps and fluorescent lamp ballasts are designed
to give their best performance at 25° C, they will provide
reasonably good light output down to 10° C (50° F) for
standard lamps and 1 6° C (60° F) for energy saving lamps.
Further decreases in ambient temperature will result in decreased
light output.
Such variables as humidity, line voltage, fixture design and
variations within the particular design of the lamp and the fluorescent
lamp ballast play an important part in determining the low temperature
starting limit.
The 800 MA and 1500 MA lamps with their higher bulb wall temperatures
are recommended for most efficient cold weather operation. Even
with high output fluorescent lamps, satisfactory operation of
the lamps depends upon adequate shielding to permit them to reach
recommended operating temperatures. Care must also be exercised
in fixture designs for the prevention of overheating of the fluorescent
lamp ballast in summertime operation.
VENTILATION
A fluorescent lamp ballast, like other electrical equipment,
generates heat during normal operation. Underwriters' Laboratories
stipulates that the temperature limitation of a ballast using
Class A insulation in normal operation should have a maximum
ballast coil temperature of 1 05¡C (221 ¡F) and a
maximum ballast case temperature of 90¡C (1 94¡F)
at its hottest spot. Ballast life will be reduced if it is operated
at temperatures above these limits.
Possible causes for an increase in ballast temperature include
higher than design supply voltage, ambient temperature, ceiling
material, distance of fixture from ceiling and enclosed vs. open
fixtures, as described in the following sections.
Where more than one ballast is installed in an enclosure, the
ballasts should be positioned far enough apart to allow for the
combined normal heating effects. To assist in limiting the temperature
rise of ballasts, the following procedures are recommended:
- Mount ballast with maximum number of sides in direct contact
with metal channel of fixture. Radiators are an excellent means
of dissipating heat.
- Provide fixture ventilation.
- Paint the unpainted fixture channels with a nonmetallic finish
to increase radiation.
- Place the ballast in a cooler location outside the fixture.
- Place fixture to attain maximum dissipation of heat by conduction,
convection or radiation.
BETTER BALLAST PERFORMANCE/LONGER LIFE
The fluorescent lamp ballast has been called the heart of the
lighting unit. As important as the ballast is, this vital component
has been misunderstood, abused and misused. The end result, in
many applications, has been premature ballast failures.
When properly applied, a fluorescent lamp ballast can be one
of the most reliable components in an electrical system
The following pages illustrate and explain the effects of the
many variables in a lighting installation. By understanding these
effects and following the guidance provided, better ballast performance
and longer ballast life will result.
EFFECT OF VOLTAGE
A ballast is tested in a lighting unit at rated voltages, e.g.,
l 20V, 277V However, voltage variations can exist in any installation.
Voltages as high as 1 27V to 1 30V operating a ballast rated
at 1 20V are common. In new construction, the voltage can become
excessive until the electrical system is fully loaded. Lighting
is usually installed before the other heavy electrical equipment
which will normally reduce voltage.
The ballast industry rates ballasts for ± 7 1/2% voltage
variation for electromagnetic ballasts and ± 10% for electronic
ballasts. This, however, pertains only to the electrical characteristics
of the ballast - not its thermal characteristics. As voltage
above nominal is applied, the ballast operating temperature increases.
Test results for a 120V ballast fixture combination shows for
every 1V increase the ballast case temperature increases approximately
0.8° C.
Considering that for every 10¡C temperature increase ballast
life will be cut in half, excessive voltage increase will decrease
the life of a ballast.
EFFECT OF AMBIENT TEMPERATURE
All fluorescent lighting units are tested in an ambient temperature
of 25° C, which supposedly duplicates the temperature in
a normal lighting installation. Yet in new construction before
the air conditioning is turned on, or in industrial plants which
are not air conditioned, it is not uncommon to have ambient temperatures
as high as 40° C to 50° C at the lighting unit location.
This higher ambient will, of course, greatly affect ballast
operating temperatures. How much? In a sample fixture ballast
combination, a 1° C ambient rise causes a 0.9° C rise
in ballast case temperature. Thus, in a 30° C ambient, the
ballast case temperature will rise 4.5° C. In a 40° C
ambient, the temperature will rise 13.5° C.
EFFECT OF CEILING MATERIAL
Underwriters' Laboratories, Inc. specifies a pine board material
be used to test surface-mounted lighting units, except in the
cases of low density ceiling mounting. The majority of ceilings
used in construction today are some variation of acoustical tile,
all of which have a different rate of heat dissipation.
Extensive tests prove conclusively there can be a 10° C
variation between a pine board ceiling and various commonly used
acoustical ceilings.
Underwriters' Laboratories, Inc. also calls for a recessed lighting
unit to be heat tested in a wooden enclosure which represents
the wall or ceiling cavity in which the unit is to be installed.
Normally, this should present no problem. However, there have
been numerous occasions where an insulation fiber glass material
is placed over the recessed lighting unit.
Tests indicate there is a minimum of a 10° C rise between
the U.L. test enclosure and the extreme fiber glass enclosure.
The type of mounting for fixtures is important. Many lighting
units are designed so they can be either surface mounted on the
ceiling or suspended.
The distance the lighting unit is suspended below the ceiling
greatly affects the ballast operating temperature. Tests indicate
a ballast case temperature variation of 22.50C between a close-ceiling
mounted lighting unit and a unit suspended 6 inches from the
ceiling.
Suspension distances greater than 6 inches have no appreciable
effect on ballast case temperature. However, if a unit is suspended
1 1/2 to 2 inches from the ceiling, the ballast case temperature
will still operate 10° C to 14° C cooler than a surface-mounted
unit.
FIXTURE DESIGN
Today, lighting fixture designs permit a unit to be installed
as a bare lamp (without shielding) or totally enclosed (100%
shielding) unit. The methods of shielding the lamps in a lighting
unit are many, varied and too numerous to evaluate here.
Tests taken at the extremes, e.g., the difference in ballast
operating temperatures in a bare lamp unit and a plastic wrap-around
unit can run as high as 14.5° C.
In a louvered lighting unit, the ballast case temperature runs
between these two extremes depending upon the size of the louver
cells.
EFFECT OF LIGHT OUTPUT AND OTHER FACTORS
Ballast tests indicate there can be a 4°C variation in the
case temperature of a certified ballast (CBM) which provides
95% light output versus a CBM ballast which provides 100% light
output.
Ballast material variations can also result in slight ballast
temperature variations no matter how rigidly they are controlled.
Other uncontrollable variations which can affect ballast temperatures
include lamp tolerances, ballast case contact with the lighting
unit, and thickness of lighting unit metal.
ACCUMULATED EFFECT OF VARIABLES
As a test fixture, consider a typical four lamp plastic wraparound
unit in an ambient of 25° C, a voltage of 120 volts, and
a U.L. pine wood ceiling mounting. Assume the ballast case temperature
is 87° C under these conditions. In actual application the
lighting unit is surface-mounted to an acoustical tile ceiling
in a 30° C ambient and supplied by a 125 volt circuit.
A buildup of all these unfavorable variations can cause the
case temperature of the ballast to reach 1 08° C. This places
the protector within the ballast in the critical temperature
zone and the protector will probably open.
In this case, the lamps and ballast will be taken out of the
circuit until the unit has cooled to the protector's reclosing
temperature. The protector reactivates the ballast, permitting
corrective action to be taken without the necessity of ballast
replacement.
TROUBLESHOOTING
ELECTRICAL TEST EQUIPMENT
Note: Voltage and current measurements present the possibility
of exposure to hazardous voltages and should be performed only
by qualified personnel.
The following equipment is recommended for testing fluorescent
fixtures:
True RMS Voltmeter
Ranges: 0-300-1000 Volts AC
Ammeter (clamp-on type acceptable)
Ranges: 0-10 Amperes AC
Multi-meter (with voltage and current ratings as shown above)
Frequency: 60Hz for electromagnetic, above 20kHz for electronic
TROUBLESHOOTING FLUORESCENT APPLICATIONS
SAFETY FIRST: Troubleshooting procedures must
take place within these guidelines:
- Those working on the fixtures (and hence, in situations where
they may be exposed to hazardous voltages) must be properly
qualified to perform such work.
- Ballasts, starters, capacitors and fixtures must be grounded
in accordance with the National Electrical Code (NEC). In the
case of fluorescent ballasts, the case must be grounded either
to the fluorescent fixture or, if remote mounted, by other
means such as a wire from ballast case to ground. Without proper
fixture and ballast grounding, a shock hazard may exist due
to the fluorescent fixture becoming energized by an internal
ballast failure. In addition, all ballasts have normal leakage.
When the ballast is properly grounded, the leakage current
does not constitute a hazard.
- Any work performed on the lighting system, including inspection,
troubleshooting and maintenance, should be done with the fixture
properly de-energized and the circuit locked and tagged according
to Occupational Safety and Health Act (OSHA) requirements.
INOPERATIVE FIXTURE
Often when a fixture becomes inoperative, the cause is not attributable
to the ballast. It is therefore important to examine all components
of the fixture before removing the ballast for replacement. The
following procedure is recommended:
- Change or check all lamps to ensure satisfactory operation.
- As lamps are removed, examine all sockets to ensure proper
and positive contact with lamp pins.
- If starters are used, each starter should be checked and
replaced wherever necessary.
- Examine all connections within the fixture to ensure their
conformance with the wiring instructions appearing on the ballast.
- Examine and test ballast.
CYCLING
The National Electrical Code® stipulates that most ballasts
installed indoors must contain a cut-out device that protects
the ballast from overheating.
If abnormal ambient conditions cause the ballast to overheat,
the thermal protection device's switch disconnects the ballast
from the line.
Once cooled, the ballast is reconnected and restarts the lamps.
If the conditions persist, the ballast will switch off again
repeatedly in a process called "cycling."
LAMP "SWIRLING"
Another problem that may occur is a process known as swirling
or spiraling, where light does indeed appear to swirl or spiral
inside the tube. This is normal for some lamps when first lighted,
and in these cases the problem will correct itself after a few
hours of operation.
- This problem may also be caused by cold temperatures. In
this case, the lamps may need to be jacketed or otherwise shielded
from the cold drafts. Also, check that the lamps are rated
for the actual temperature measured.
- This problem may also be caused by low input voltage; check
and correct.
- Next, check for ballast and lamp compatibility and replace
the wrong component.
- Replace lamp with known good lamp. If condition still exists,
change ballast.
To measure starting current and operating current, the ammeter
must be connected between the colored high voltage secondary
lead of the ballast and the lamp.
To determine starting voltage, remove lamp and connect voltmeter
between respective primary and secondary leads of each lamp according
to ballast wiring diagram.
Lamp Type |
Operating Current (Ampere) |
Starting Current (Ampere) |
Starting Voltage
(Minimum Open Circuit) |
F4T5 |
.17 |
.16-.25 |
108 |
F6T5 |
.16 |
.16-.25 |
108 |
F8T5 |
.145 |
.16-.25 |
108 |
F13T5 |
.165 |
.18-.27 |
180 |
F14T8 |
.365 |
.44-.65 |
108 |
F14T12 |
.38 |
.44-.65 |
108 |
F15T8 |
.305 |
.44-.65 |
108 |
F15T12 |
.325 |
.44-.65 |
108 |
F18T8 |
.385 |
.35-.80 |
108 |
F19T8 |
.355 |
.35-.80 |
108 |
F20T12 |
.38 |
.44-.65 |
108 |
F25T12 |
.46 |
.41-.95 |
108 |
F30T8 |
.355 |
.40-.95 |
176 |
F40T12 |
.43 |
.55-.75 |
176 |
F90T17 |
1.50 |
1.45-2.20 |
132 |
TROUBLESHOOTING PREHEAT INSTALLATIONS
One of the major causes of trouble with a Preheat circuit is
the miswiring of the fluorescent ballast. This condition can
be noted by short lamp or starter life, non-starting of lamp,
or premature failure of the ballast. For example, with a two
lamp ballast, the starter leads from the two pairs of lamp holders
may be crossed. If both starters open at the same time, the lamps
will start. However, if one lamp starts before the other, the
nonstarting lamp may blink on and off for a long time before
starting if it will start at all.
To determine if wired correctly, short the terminals of a fluorescent
starter with a fine bare wire. Remove all starters from the fixture
but leave the lamps in. Insert the shorted starter in one starter
slot. If the fixture is wired properly both ends of the same
lamp will glow. If it is crosswired, one end of each lamp will
glow.
There have been many installations of Preheat fluorescent lighting
in which two lamp ballasts are operating with one lamp on and
one lamp out, or with shorted starters. These conditions will
cause premature ballast failures due to the ballast coils being
operated above their coil temperature limitation. Thus it is
advisable that all inoperative lamps and starters be immediately
replaced.
Other causes of difficulty could be (1) low or high circuit
voltage, (2) improper lamp holder contact, (3) pinched wires
or (4) improper lamps.
VIII. SLIMLINE & INSTANT
START
To determine starting voltage, the lamp must be removed and
voltmeter connected between the respective primary and secondary
leads of each lamp as designated on ballast label. For series-sequence
ballasts, the red lead must be in position while measuring the
starting voltage of the remaining lamp.
LAMP TYPE |
*STARTING VOLTAGE
(Minimum) |
F24T12 |
270 |
F36T12 |
315 |
F40T12/IS |
385 |
F40T17/IS |
385 |
F42T6 |
405 |
F48T12 |
385 |
F64T6 |
540 |
F72T8 |
540 |
F72T12 |
475 |
F96T8(200mA) |
675 |
F96T8(200mA) |
675 |
F96T12 |
565 |
For Single Lamp, measure voltage between Red & White
leads.
For Two Lamp (SERIES SEQUENCE), measure voltage between
Red & White
Insert lamp in Red & White position, then read voltage between
Blue & Black
For Two Lamp (Lead Lag), measure voltage between Red & White
and Blue & White Leads.
For Electronic (parallel), measure voltage between Red & Blue
leads.
TROUBLESHOOTING SLIMLINE & INSTANT START INSTALLATIONS
There are two common electromagnetic ballast circuits for the
two lamp operation of Slimline lamps: The Lead Lag circuit and
the Series Sequence circuit. Electronic ballasts operate the
lamps in parallel.
The Lead Lag Slimline Ballast operates one lamp independently
of the other. Thus, if one lamp becomes inoperative, the other
lamp will still light. There are two legs in the Lead Lag circuit:
one leg of the circuit is called the lead section and contains
an inductive coil and a capacitor in series with the lamp. The
other leg just contains an inductive coil and is called the lag
section. This is how the name "Lead Lag" was derived.
It is permissible to use Lead Lag Slimline Ballasts for starting
of Slimline lamps down to temperature of 0° F and above.
The Series Sequence Slimline Ballast was introduced in order
to reduce the size, weight, and cost of the Slimline Ballast.
In this circuit two lamps are operated in series, with the lamps
starting in sequence. If one lamp becomes inoperative the other
will not fully light or light all.
Short lamp life or premature end blackening can be due to (1)
low supply voltage, (2) improper lamp-socket contact or (3) miswiring
and eventually fail.
The open circuit voltage of a Slimlline Ballast, in many cases,
is great enough to start a lamp with one lamp filament de-activated.
This lamp will become extremely black at one end and flicker.
If the lamp is not replaced, the ballast will overheat and eventually
fail.
If an Electromagnetic Slimline Ballast is operated with one
lamp on and one lamp off, the ballast will experience higher
coil temperatures which could result in premature ballast failures.
In cases of short ballast life generally are not effected by
lamp failure.
To measure starting voltage, connect voltmeter between the highest
reading Red lead and Blue lead with lamp removed.
To measure filament voltage on a single lamp unit, read between
Red-Red and Blue-Blue leads. For two lamp units, read voltage
between Red-Red, Blue-Blue and Yellow-Yellow leads.
Rapid Start - 430 MA. Lamp Type |
Starting Voltage
(Minimum @50° F) |
Filament Voltage |
Single Lamp |
Two Lamp |
|
F14T12 |
108 |
157 |
7.5-9.0 |
F15T8 |
108 |
157 |
7.5-9.0 |
F15T12 |
108 |
157 |
7.5-9.0 |
F20T12 |
108 |
157 |
7.5-9.0 |
F17T8 |
140 |
210 |
3.4-4.5 |
F25T8 |
170 |
260 |
3.4-4.5 |
F25T12 |
200 |
256 |
3.4-4.5 |
F30T12 |
150 |
215 |
3.4-4.5 |
F32T8 |
200 |
300 |
3.4-4.5 |
F40T8 |
250 |
385 |
3.4-4.5 |
F40T10 |
200 |
256 |
3.4-4.5 |
F40T12 |
200 |
256 |
3.4-4.5 |
FC6T9 |
150 |
225 |
3.4-4.5 |
FC8T9 |
180 |
--- |
3.4-4.5 |
FC12T9 |
200 |
--- |
3.4-4.5 |
FC16T9 |
205 |
--- |
3.4-4.5 |
FC8T9 & FC12T9 |
--- |
230 |
3.4-4.5 |
FC12T9 & FC16T9 |
--- |
230 |
3.4-4.5 |
Rapid-Start 800 & 1500 MA.
Lamp Type |
STARTING VOLTAGE
(MINIMUM) |
Single Lamp |
Two Lamp |
Filament Voltage |
50° F |
0° F |
-20° F |
50° F |
0° F |
-20° F |
|
F24T12/HO |
85 |
110 |
140 |
145 |
195 |
225 |
3.4-4.5 |
F36T12/HO |
115 |
155 |
190 |
195 |
235 |
260 |
3.4-4.5 |
F48T12/HO |
155 |
203 |
240 |
256 |
290 |
310 |
3.4-4.5 |
F60T12/HO |
210 |
240 |
290 |
325 |
350 |
365 |
3.4-4.5 |
F72T12/HO |
260 |
283 |
340 |
395 |
410 |
420 |
3.4-4.5 |
F84T12/HO |
280 |
330 |
360 |
430 |
445 |
455 |
3.4-4.5 |
F96T8/HO |
450 |
--- |
--- |
775 |
--- |
--- |
3.6-4.8 |
F96T12/HO |
295 |
330 |
360 |
465 |
480 |
490 |
3.4-4.5 |
|
|
|
|
|
|
|
|
F48PG17/VHO |
160 |
205 |
240 |
250 |
265 |
300 |
3.4-4.5 |
F48T12/VHO |
160 |
205 |
240 |
250 |
265 |
300 |
3.4-4.5 |
F72PG17/VHO |
225 |
270 |
310 |
350 |
360 |
400 |
3.4-4.5 |
F72T12/VHO |
225 |
270 |
310 |
350 |
360 |
400 |
3.4-4.5 |
F96PG17/VHO |
300 |
355 |
400 |
470 |
470 |
500 |
3.4-4.5 |
96T12/VHO |
300 |
355 |
400 |
470 |
470 |
500 |
3.4-4.5 |
Note: Electronic ballasts generally provide starting
voltages higher than those listed in the above tables. These
open circuit voltages are listed on the ballast's label. Filament
voltages for electronic and electromagnetic ballasts are the
same.
TROUBLESHOOTING RAPID START INSTALLATIONS
The Rapid Start circuit eliminates the annoying flicker associated
with starting Preheat systems. Rapid Start circuits also simplify
maintenance since no starter is used.
The Rapid Start lamp operates on the principle of utilizing
a starting voltage which is insufficient to start the lamps while
the cathodes are cold but is sufficient to start the lamps when
the cathodes are heated to maintain emission temperature. This
voltage range between starting cold and starting hot is a very
narrow band of voltage which must be closely controlled in order
to prevent either failure of the lamps to start or instant starting
of the lamps with cold cathodes which is detrimental to the lamps.
In order to stay within this range of voltage, it is necessary
to excite the gas within the lamps by means of an external voltage
which is applied to the gas within the lamps to create ionization.
This external excitation is created by means of the capacity
that is present
between the lamp and the reflector or channel. In order to act
effectively, the fixture must be connected to ground and the
white lead of the ballast connected to ground lead of power supply.
Thus it is stated on the label of Rapid Start ballasts "MOUNT
LAMPS WITHIN 1/2 INCH (3/4 INCH or 1 INCH) OF GROUNDED METAL
REFLECTOR."
The majority of new fluorescent installations today use ballasts
of the Rapid Start design. The HIGH OUTPUT (800 MA), and VERY
HIGH OUTPUT (1500 MA) lamps are of the Rapid Start design.
BLUE-BLUE, YELLOW-YELLOW, RED-RED LEADS are the built-in filament
windings which supply a voltage of 3.4 to 4.5 volts to the lamp
cathodes. If the cathodes are not properly heated, premature
lamp end blackening will result. The lack of heating could be
due to:
1. Improper seating of the lamp within the socket.
2. Broken sockets.
3. Broken lamp pins.
4. Too great of socket spacing.
5. Damaged lamp cathode(s).
6. Ballast lead wire not properly connected to socket.
7. Low supply voltage.
8. Inadequate ballast filament voltage.
9. Improper wiring.
To determine if there is adequate voltage at the lamp cathodes,
measure the voltage at the socket terminals. The voltage at the
sockets should read between 3.4 and 4.5 volts. If there is adequate
voltage, the lamp end blackening can be due to conditions 1,
2, 3, 4, or 5. If the voltage is not adequate it can be due to
one or more of conditions 6, 7, 8, or 9.
If random starting of Rapid Start lamps is experienced, be sure
the fixture is properly grounded. As previously stated, for completely
reliable starting in Rapid Start circuits it is necessary to
have a starting aid.
The starting aid should be an electrically grounded metal strip
at least 1 inch wide and extending the full length of the lamp.
The lamp should be within 1/2 inch of the grounded step for 40
watt lamps and smaller, (3/4 inch for T8 lamps) and 1 inch for
higher output lamps.
If, under high humidity conditions, Rapid Start lamps start
or do not start at a I although the cathodes are properly heated,
this may be due to dirt on the lamps which is offsetting the
silicon coating on the lamps, or t may be due entirely to a poor
silicon coating. If t is a new installation (in operation only
a few months) which experiences random starting under high humidity
conditions, in most cases n will be due to low supply voltage
or poor silicon coating on the lamps.
When random starting is experienced under high humidity conditions
in an installation in operation for a longer period of time this
is usually due to dirt on the lamps. The lamps should be washed
in water to remove the dirt.
Sometimes with a two lamp Rapid Start series ballast only one
lamp will light to full brilliance and the other will not light.
Refer to the figure below. If the lamp between the Red leads
and Yellow leads is lit and the other lamp is out, look for a
pinched Yellow lead. If the lamp between the Red and Yellow leads
does not light and the other does, t is probably due to a short
within the ballast.
MODIFIED RAPID START
This type of ballast starts and operates the lamps similar to
Rapid Start Ballasts, so troubleshooting on pages 44-48 would
also apply. The only difference is that filament heating is reduced
or eliminated after the lamps ignite so the 3.4-4.5 volts specified
cannot be measured during normal operation. Also, some two lamp
ballasts require that only one lamp be removed when measuring
starting and filament voltages. If both lamps are removed, these
voltages cannot be accurately measured.
INSTANT OF RAPID START LAMPS START
This type of ballast does not provide filament heating to the
lamps. Only the starting voltage which is listed on the ballast
label can be measured when the lamp is removed. The wiring of
this ballast requires that the lamp filaments be shorted together
and then connected to the ballast to obtain rated lamp life.
If the filaments are not shorted, the lamps will ignite properly
but fail prematurely. Rated lamp life when using this Instant
Start Ballast may be reduced vs. a Rapid Start Ballast last depending
on how frequently the lamps are started. |